Provide enough information to allow the selection of the manufacturer product to meet requirements. This information may also be used to replace the installed product during the operation stage of the building's lifecycle. Information covering the execution of the deliverable should also be provided in the associated specification.
Name |
Definition |
|
Manufacturer |
The Manufacturer of the Static inverter power supply units. |
|
Standard |
An example value being To BS EN 50171. |
|
Third party certification |
An example value being ICEL 1009. |
|
Mode of operation |
An example value being Changeover mode. |
|
Integral maintenance bypass |
An example value being Required. |
|
Input - Nominal voltage |
An example value being Single phase 230 V a.c. ±10%. |
|
Input - Nominal frequency |
An example value being 50 Hz. ±2%. |
|
Battery charger - Type |
An example value being Electronic solid-state controller, constant voltage, current-limited. |
|
Battery charger - Battery recharge time |
An example value being To 80% capacity within 12 hours and 100% capacity within 24 hours. |
|
Change over contactor |
An example value being To BS 764. |
|
Inverter output - Load compatibility |
An example value being Suitable for use with loads operating at any power factor, leading or lagging up to 0.9. |
|
Inverter output - Rated output apparent power |
An example value being 1.25 kV·A. |
|
Inverter output - Nominal voltage |
An example value being Single phase 230 V a.c. ±10%. |
|
Inverter output - Voltage waveform |
An example value being Sinusoidal. |
|
Inverter output - Voltage harmonic distortion |
An example value being <2% with linear load. |
|
Inverter output - Nominal frequency |
An example value being 50 Hz ±1%. |
|
Controls, indicators and alarms - Status indicators - Indicate the following with green LED |
An example value being a.c. mains input to battery charger. |
|
Controls, indicators and alarms - Status indicators - Indicate the following with amber LED |
An example value being Boost charge. |
|
Controls, indicators and alarms - Status indicators - Indicate the following with red LED |
An example value being Battery charger failure. |
|
Controls, indicators and alarms - LCD display |
An example value being Battery voltage. |
|
Controls, indicators and alarms - Event log |
An example value being Record up to 64 fault occurrences including time and date for each occurrence. Provide user access to event log through LCD display. |
|
Audible alarms - Type |
An example value being Integral alarm within central battery enclosure providing minimum 65 dBA at 1 m. |
|
Audible alarms - Activation and reset |
An example value being Activated by any fault condition. Continuous output until fault cleared or alarm silenced. Silencing of the alarm must not clear LED status indication. |
|
Common fault relay contact |
An example value being Volt free 230 V a.c. |
|
Enclosure - Mounting arrangement |
An example value being Floor standing. |
|
Enclosure - Ingress protection (minimum) |
An example value being To BS EN 60529, IP21. |
|
Enclosure - Material and construction - Type |
An example value being Welded carbon steel. Assemble to prevent distortion when the complete enclosure is lifted or transported. |
|
Enclosure - Material and construction - Finish |
An example value being Epoxy powder coated. |
|
Enclosure - Material and construction - Colour |
The Enclosure - Material and construction - Colour of the Static inverter power supply units. |
|
Enclosure - Lockable access doors |
An example value being Required. |
|
Enclosure - Cable entry |
An example value being Removable gland plates, for top entry cables. |
|
Enclosure - Ventilation arrangement |
An example value being Forced ventilation fans during emergency mode. |
|
Enclosure - Fan failure alarms |
An example value being Required. |
|
Enclosure - Noise emission - Sound pressure level in normal mode (maximum) |
An example value being 60 dBA at 1 m. |
|
Enclosure - Noise emission - Sound pressure level in battery mode (maximum) |
An example value being 65 dBA at 1 m. |
|
System efficiency (minimum) |
An example value being 85%. |
|
Battery - Type |
An example value being Lead-acid Planté cells. |
|
Battery - Labelling |
An example value being Indelibly mark with year of manufacture and installation. |
|
Accessories |