Provide enough information to allow the selection of the manufacturer product to meet requirements. This information may also be used to replace the installed product during the operation stage of the building's lifecycle. Information covering the execution of the deliverable should also be provided in the associated specification.
Name |
Definition |
|
Manufacturer |
The Manufacturer of the Generator sets. |
|
Standard |
An example value being To BS ISO 8528-5. |
|
Internal combustion engine - Standards - Generally |
An example value being To BS ISO 8528-2. |
|
Internal combustion engine - Standards - Overspeed protection |
An example value being To BS ISO 3046-6. |
|
Internal combustion engine - Engine type |
An example value being Compression-ignition. |
|
Internal combustion engine - Air and fuel intake - Type |
An example value being Naturally aspirated. |
|
Internal combustion engine - Air and fuel intake - Air filters |
The Internal combustion engine - Air and fuel intake - Air filters of the Generator sets. |
|
Internal combustion engine - Air and fuel intake - Fuel filters |
The Internal combustion engine - Air and fuel intake - Fuel filters of the Generator sets. |
|
Internal combustion engine - Lubrication - Oil filters |
The Internal combustion engine - Lubrication - Oil filters of the Generator sets. |
|
Internal combustion engine - Lubrication - Crankcase oil heater |
An example value being Required. |
|
Internal combustion engine - Lubrication - Drain valve |
The Internal combustion engine - Lubrication - Drain valve of the Generator sets. |
|
Internal combustion engine - Lubrication - Oil reservoir tank |
An example value being Provide with a 2 L capacity; include oil level monitoring and a drain valve located to facilitate gravity oil removal. |
|
Internal combustion engine - Cooling system - Cooling medium |
An example value being Air. |
|
Internal combustion engine - Cooling system - Radiator |
An example value being Engine-mounted. |
|
Internal combustion engine - Cooling system - Fan |
An example value being Electric motor driven and remote-mounted. |
|
Internal combustion engine - Cooling system - Coolant heater |
An example value being Required. |
|
Internal combustion engine - Cooling system - Drain valve |
The Internal combustion engine - Cooling system - Drain valve of the Generator sets. |
|
Internal combustion engine - Engine starting method |
An example value being Compressed air. |
|
Alternator - Rated power output |
An example value being 50 kV A. |
|
Alternator - Format |
An example value being Asynchronous. |
|
Alternator - Excitation |
An example value being Self. |
|
Alternator - Short-circuit withstand capability (minimum) |
An example value being 2.5 times full load, short-circuit current for 5 s. |
|
Alternator - Protection |
The Alternator - Protection of the Generator sets. |
|
Alternator - Overspeed withstand |
The Alternator - Overspeed withstand of the Generator sets. |
|
Alternator - Thermal classification |
The Alternator - Thermal classification of the Generator sets. |
|
Alternator - Ingress protection (minimum) |
An example value being To BS EN IEC 60034-5, IP 21. |
|
Alternator - Anti-condensation heaters |
An example value being Required. |
|
Alternator - Output cable terminal boxes - Configuration |
The Alternator - Output cable terminal boxes - Configuration of the Generator sets. |
|
Alternator - Output cable terminal boxes - Outgoing cable entry |
An example value being Bottom. |
|
Control systems - Standards - Generally |
An example value being To BS ISO 8528-4 and in accordance with. |
|
Control systems - Standards - Speed governing |
An example value being To BS ISO 8528-5 and BS ISO 3046-4. |
|
Control systems - Standards - Voltage regulation |
An example value being To BS ISO 8528-5 and BS 4999-140. |
|
Control systems - Enclosure - Mounting position |
An example value being Integral to the generating set. |
|
Control systems - Enclosure - Ingress protection (minimum) |
An example value being To BS EN 60529, IP22. |
|
Control systems - Enclosure - Material |
The Control systems - Enclosure - Material of the Generator sets. |
|
Control systems - Enclosure - Finish |
The Control systems - Enclosure - Finish of the Generator sets. |
|
Control systems - Enclosure - Colour |
The Control systems - Enclosure - Colour of the Generator sets. |
|
Control systems - User interface |
An example value being LCD alphanumeric display with integrated operation keys and LED indication. |
|
Control systems - Control functions |
An example value being Alphanumeric display with navigation buttons. |
|
Control systems - Measurement and indication - Engine |
An example value being Engine coolant temperature. |
|
Control systems - Measurement and indication - Alternator |
An example value being Alternating current for each phase. |
|
Control systems - Measurement and indication - Status |
An example value being Coolant heater on. |
|
Control systems - Protection - Engine |
An example value being Battery charger malfunction alarm. |
|
Control systems - Protection - Alternator |
An example value being Earth fault shutdown. |
|
Control systems - Alarms |
An example value being Audible and visual with common audible reset. |
|
Control systems - Communications interface |
An example value being Auxiliary output relays. |
|
Control systems - Features |
The Control systems - Features of the Generator sets. |
|
Sub-base fuel tank - Capacity (minimum) |
The Sub-base fuel tank - Capacity (minimum) of the Generator sets. |
|
Sub-base fuel tank - Tank type |
An example value being Steel double skinned, mounted integral to the generator base frame. |
|
Accessories |
An example value being Air intake manifold heaters. |
|