Provide enough information to allow the selection of the manufacturer product to meet requirements. This information may also be used to replace the installed product during the operation stage of the building's lifecycle. Information covering the execution of the deliverable should also be provided in the associated specification.
Name |
Definition |
|
Manufacturer |
The Manufacturer of the Automatic sprinkler pump control panels. |
|
Standard |
An example value being In accordance with BS 8458. |
|
Third party certification |
The Third party certification of the Automatic sprinkler pump control panels. |
|
Enclosure - Ingress protection (minimum) |
An example value being To BS EN 60529, IP54. |
|
Enclosure - Mechanical protection (minimum) |
An example value being To BS EN 62262, IK08. |
|
Enclosure - Material |
An example value being Polycarbonate. |
|
Enclosure - Finish |
An example value being Externally polyester powder coated. |
|
Enclosure - Colour |
The Enclosure - Colour of the Automatic sprinkler pump control panels. |
|
Enclosure - Doors and panels - Form |
An example value being Right angle return construction with rounded edges and corners, concealed hinges and internal gaskets. |
|
Enclosure - Doors and panels - Swing |
An example value being 90°. |
|
Enclosure - Doors and panels - Hardware |
An example value being Corrosion-resistant lever type handles with latching mechanism. |
|
Enclosure - Doors and panels - Locks |
An example value being Cylinder. Standardize key type. |
|
Isolator - Standard |
An example value being To BS EN 60947-1 and. |
|
Isolator - Type |
An example value being Switch-disconnector. |
|
Isolator - Rated operational voltage (Ue) |
An example value being 230 V a.c. |
|
Isolator - Rated operational current (In) |
An example value being 32 A. |
|
Isolator - Rated operational frequency |
An example value being 50 Hz. |
|
Isolator - Number of poles |
An example value being Triple. |
|
Isolator - Rated short-time withstand current (Icw) for 1 s |
The Isolator - Rated short-time withstand current (Icw) for 1 s of the Automatic sprinkler pump control panels. |
|
Isolator - Utilization category |
An example value being AC-23A. |
|
Isolator - Terminals |
An example value being Suitable for the connection of copper conductors. |
|
Isolator - Mechanical interlocking |
An example value being Door-interlocked operating handles. |
|
Contactors - Standard |
An example value being To BS EN IEC 60947-4-1. |
|
Contactors - Rated operational voltage (Ue) |
An example value being 230 V a.c. |
|
Contactors - Rated operational current (In) |
An example value being 32 A. |
|
Contactors - Rated operational frequency |
An example value being 50 Hz. |
|
Contactors - Utilization category |
An example value being AC-3. |
|
Contactors - Number of poles |
An example value being Triple. |
|
Circuit protection |
An example value being Via HRC fuses capable of carrying the start current for a period of no less than 20 s. |
|
No volt release |
An example value being Automatic resetting following supply failure. |
|
Control panel - Functions |
An example value being Automatic pump start initiated by de-energized pressure switch signal. Continuous pump running until manual initiated shut down. |
|
Control panel - Visual indicators |
An example value being Green LED for healthy condition. |
|
Control panel - Audible alarms |
An example value being 75 dB minimum at 1 m from control panel. |
|
Control panel - Display the following conditions |
An example value being Green LED indicating a.c. supply healthy on each phase. |
|
Metering functions |
An example value being Ammeter capable of measuring full load current of pump motor with overload scale of six times full load current. |
|
Labelling |
The Labelling of the Automatic sprinkler pump control panels. |
|