Provide enough information to allow the selection of the manufacturer product to meet requirements. This information may also be used to replace the installed product during the operation stage of the building's lifecycle. Information covering the execution of the deliverable should also be provided in the associated specification.
Name |
Definition |
|
Manufacturer |
The Manufacturer of the Mechanical services control panels. |
|
Enclosure - Ingress protection (minimum) |
An example value being To BS EN 60529, IP44. |
|
Enclosure - Mechanical protection (minimum) |
An example value being To BS EN 62262, IK05. |
|
Enclosure - Material |
An example value being Polycarbonate. |
|
Enclosure - Finish |
An example value being Externally polyester powder coated. |
|
Enclosure - Colour |
The Enclosure - Colour of the Mechanical services control panels. |
|
Enclosure - Doors and panels - Form |
An example value being Right angle return construction with rounded edges and corners, concealed hinges and internal gaskets. |
|
Enclosure - Doors and panels - Swing |
An example value being 90°. |
|
Enclosure - Doors and panels - Hardware |
An example value being Corrosion-resistant lever type handles with latching mechanism. |
|
Enclosure - Doors and panels - Locks |
An example value being Cylinder, with standardized key type. |
|
Isolator - Standard |
An example value being To BS EN 60947-3. |
|
Isolator - Type |
An example value being Switch-disconnector to BS EN 60947-3. |
|
Isolator - Rated operational current (In) |
An example value being 16 A. |
|
Isolator - Rated operational voltage (Ue) |
An example value being 250 V. |
|
Isolator - Rated operational frequency |
An example value being 50 Hz. |
|
Isolator - Number of poles |
An example value being Double. |
|
Isolator - Rated short-time withstand current (Icw) for 1 s |
The Isolator - Rated short-time withstand current (Icw) for 1 s of the Mechanical services control panels. |
|
Isolator - Utilization category |
An example value being AC-21A. |
|
Isolator - Rated short-circuit making capacity (Icm) |
The Isolator - Rated short-circuit making capacity (Icm) of the Mechanical services control panels. |
|
Isolator - Terminals |
An example value being Suitable for the connection of copper conductors. |
|
Isolator - Rated short-circuit breaking capacity (Icu) |
An example value being 25 kA. |
|
Isolator - Mechanical interlocking |
An example value being Door-interlocked operating handles. Rotary handle. |
|
Internal separation |
An example value being 2 type 1. |
|
Cable entry |
An example value being Suitable for front access cabling. Entry via gland plates facilitating either top and/or bottom entry. |
|
Gland plate gaskets |
An example value being Match the assembly’s degree of ingress protection. |
|
Internal cable zones |
An example value being Sufficient to allow cabling to be neatly routed and terminated. |
|
Interconnecting cable |
An example value being Single core PVC insulated cables to BS 6231. |
|
Terminals - Mounting |
An example value being Suitable for mounting to 35 mm DIN rail. |
|
Terminals - Identification - Neutral and earth bar terminals |
An example value being Label with the outgoing circuit reference. |
|
Terminals - Identification - Cable terminations |
An example value being Label with circuit reference, with push-on plastics markers. |
|
Trunking - Standard |
An example value being To BS EN 50085-2-3. |
|
Trunking - Material |
An example value being PVC-U. |
|